Current location - Recipe Complete Network - Catering industry - Some dining room equipment, lighting, including some three-phase equipment in the kitchen, add up to 200kw. What specifications of cables are needed to introduce the main line? such as
Some dining room equipment, lighting, including some three-phase equipment in the kitchen, add up to 200kw. What specifications of cables are needed to introduce the main line? such as
The calculated current of 200kW equipment is 360A (power factor is 0.85).

Therefore, it is recommended to select duplex cable 2x(4x 120+ 1x70) for incoming line specifications (there is a surplus).

Or choose duplex cable 2x(4x95+ 1x50) (a little tight).