Installation requirements of catering concealed spraying equipment
This is the requirement of installing fire sprinklers in building codes. Have a nice day.

People's Republic of China (PRC) national standard * * * GBP GB500 16—2006 Code for Fire Protection Design of Buildings.

8.5

Location of automatic fire extinguishing system

8.5. 1

The following places shall be equipped with automatic fire extinguishing system, which shall be adopted unless it is not suitable for water protection or fire extinguishing, and otherwise specified in this specification.

Automatic sprinkler system:

1 50000 spindle and above cotton mill opening and cleaning workshop; Classification carding room of linen mills with 5000 spindles and above; Dry, and screening match factory part; Pre-production, molding, slicing and embossing of foam plastic factory; Woodworking workshop, area1500m2; /kloc-Single-storey and multi-storey factories for shoes, clothing, toys and electronics with a total construction area of more than 0/500m2 or 3000m2; High-rise class C factory building; The preparation part of the aircraft engine test bed; The building area exceeds 500m2.

Class C underground workshop;

2 warehouses for cotton, wool, silk, hemp, chemical fiber, fur and its products with an area greater than 1000m2; The floor area of each building

A matching warehouse larger than 600m2; An empty mail bag warehouse with a construction area of more than 500 square meters in the postal building; Underground warehouse of combustible materials with a building area of more than 500m2; Elevated warehouses and high-rise warehouses for inflammable and flame-retardant articles (except cold storage);

3./kloc-a special, first-class or other theater with more than 0/500 seats; A hall or auditorium with more than 2000 seats; More than 3000

A gymnasium with 20 seats; Lounge and equipment room for indoor staff in sports venues with more than 5,000 people;

4. Exhibition buildings, shops and hotel buildings with a building area of more than 1500m2 or a total building area of more than 3000m2,

And the ward building, outpatient building and operation department of the same building scale in the hospital; Underground shops with a building area of more than 500m2;

5. A central air-conditioning system with return air pipes (pipes) and an office building with a total construction area of more than 3000m2;

6 Underground, semi-underground, or more than four floors above the ground, or more than one, two or three floors of buildings, and the construction area of any floor is more than 300m2 (except swimming places);

7 libraries with more than 500,000 books.

8.5.2

The following parts shall be equipped with water curtain system:

1 large class, Class A class or other classes with more than 1500 seats, the stage entrance of an auditorium or auditorium with more than 2000 seats, and the doors and windows of the side platform and backstage connected to the stage;

2. Local openings that cannot be set due to fire partitions such as firewalls;

3 the upper part of the fire shutter or fire curtain that needs cooling protection.

8.5.3

The following places should be equipped with rain shower system:

Fifty two

1 match factory potassium chlorate crushing plant; A factory building that produces and uses nitrocellulose, spray-painted cotton, collodion, celluloid film and nitrocellulose with a building area greater than 100m2;

2 warehouses of nitrocellulose, spray-painted cotton, collodion, celluloid film and nitrocellulose with a building area of more than 60 square meters or a storage capacity of more than 2t;

The bottling room and actual bottle warehouse of the LPG storage and distribution station where more than 3,000 bottles are bottled on the 3rd;

4.65,438+0,500-seat grand theater, first-class theater or other theaters and 2,000-seat auditorium;

5. Studios with a building area of over 400㎡ and film studios with a building area of over 500㎡;

6. Inspection parts for blank rolling, slicing, ball grinding and ball distribution in table tennis factory.

8.5.4

The following places should be equipped with automatic fire extinguishing system and water spray fire extinguishing system:

1 Oil-immersed power transformers in factories and mines with a capacity of 40MVA or above, oil-immersed power transformers in oil-immersed power plants with a capacity of 90MVA or above, or oil-immersed power transformers in independent substations with a capacity of 125MVA or above;

2. Aircraft engine test-bed test site.

8.5.5

The following places should be equipped with automatic fire extinguishing system, and gas fire extinguishing system should be adopted:

1 population 1 10,000 or more microwave rooms, decimeter rooms and meter machines of national, provincial or city radio and television transmission towers.

Computer room, power distribution room and uninterruptible power supply (UPS) room;

2. Long-distance SPC exchange room, control room and rooms with more than 10,000 routes in international telecommunication bureaus, regional centers, provincial centers and regional centers.

Signaling transfer point room;

The SPC exchange room, control room and signaling transfer point room of the local telephone tandem office with more than 20,000 lines and the local telephone terminal office with more than 60,000 lines;

Communication rooms and control rooms of public security, disaster prevention and electric power dispatching command centers at or above the bureau level at the central and provincial levels;

5. Recording magnetic (paper) media library, located in the computer room and basic workshop, with a construction area of140m2;

Audio-visual products warehouses with a building area of not less than 120m2 in the central and provincial radio and television centers;

7. More than 6,543,800+0,000 volumes are specially collected at the national, provincial or library level; Central and provincial archives and non-

Paper files; Treasures warehouse of large and medium-sized museums; First-class paper and silk cultural relics showroom;

8 Other special and important equipment rooms. Note: When there is a standby host and a standby recording magnetic (paper) medium, which are located in different buildings or different fire zones of the same building, the pre-action automatic sprinkler system can also be used in the parts specified in paragraph 5 of this article.

8.5.6

The locations of foam fire extinguishing systems such as Class A, Class B and Class C liquid storage tanks shall conform to the current national standard Code for Design of Petroleum Depots.

GB50074, Code for Fire Protection Design of Petrochemical Enterprises GB50 160, Code for Fire Protection Design of Petroleum and Natural Gas Engineering GB50 183 and other relevant regulations.

8.5.7 In crowded places such as exhibition halls and gymnasium audience halls with a building area of more than 3000m2, and Class C workshops with a building area of more than 5000m2 that cannot use automatic sprinkler systems, fixed fire monitors and other fire extinguishing systems should be set up.

8.5.8 For catering establishments with a business area of more than 500m2 in public buildings, automatic fire extinguishing devices should be installed in the cooking hood and cooking parts in the cooking operation room, and automatic emergency cut-off devices should be installed on gas or oil pipelines.