Learn fire fighting together: easy to test for decoration and insulation.
one

Classification of combustion performance

For example, according to the test results in previous years, we still need to remember the combustion performance grades of commonly used building interior decoration materials. In the process of memorizing, we can recite A, then understand B2, and the rest is naturally B 1, which can save you a lot of time.

two

Interior decoration

The Code for Fire Protection Design of Interior Decoration of Buildings lists the combustion performance grades of decoration materials in single-storey, multi-storey, high-rise and underground civil buildings (Table 5. 1. 1, 5.2. 1, 5.3. 1). According to the exam questions, pay more attention to these forms!

three

exterior wall insulation

1. When the external wall of a building adopts an internal thermal insulation system, the thermal insulation system shall meet the following requirements:

1) For crowded places, places with fire hazards such as fire, fuel oil and gas, and places or parts such as evacuation staircases, evacuation walkways, evacuation rooms and refuge floors in various buildings, thermal insulation materials with combustion performance of Grade A should be adopted.

2) Thermal insulation materials with low smoke, low toxicity and combustion performance not lower than B 1 should be used in other places.

3) The protective layer of thermal insulation system shall be made of incombustible materials. When using thermal insulation material with combustion performance of B 1, the thickness of protective layer should not be less than10 mm. ..

4. For buildings in crowded places, the combustion performance of external thermal insulation materials for external walls should be Grade A. ..

5. The insulation materials for the internal and external walls and roofs of the following pension facilities shall be of Grade A combustion performance:

1) an independent pension institution.

2) The old-age facilities built in combination with other buildings have a total construction area of more than 500m2.

6. The decorative layer of the external wall of the building shall be made of materials with grade A combustion performance, but when the building height does not exceed 50m, grade B 1 can be adopted.

four

Fire protection requirements for decoration of special functional parts

1. Song and dance entertainment places

When installed in a single, multi-storey or high-rise civil building, the ceiling material for interior decoration should be Grade A decoration material, and other parts should be Grade B 1 decoration material; When installed in the basement, the ceiling and wall materials for interior decoration shall be Grade A decoration materials, and other parts shall be decorated with materials not lower than Grade B 1.

2. Teaching places and teaching experimental places

When installed in a single, multi-storey or high-rise civil building, the ceiling should be decorated with Grade A materials, and the wall should be decorated with materials not lower than Grade B 1; When installed in underground civil buildings, the ceiling and wall surface should adopt grade A decorative materials.

3. A room without windows

The combustion performance grade of decoration materials in windowless rooms should be improved by one level on the basis of the original regulations except grade A.

4. Exhibition halls, libraries, archives and cultural relics storage rooms

The ceiling shall be decorated with Grade A materials, and the floor shall be decorated with materials not lower than Grade B 1.

5. Computer room

Fire pump room, mechanical pressurized air supply and smoke exhaust room, steel cylinder room of fixed fire extinguishing system, power distribution room, transformer room, generator room, oil storage room, ventilation and air conditioning room, etc. All interior decoration materials shall be Grade A decoration materials. For important rooms such as fire control room, the ceiling and walls should be decorated with Grade A materials, and the floor and other decorations should be decorated with materials not lower than Grade B 1.

6. The kitchen in the building

The ceiling, wall and floor of the kitchen in the building should adopt Grade A decoration materials.

7. Restaurants and research laboratories that use naked flames

The combustion performance grade of decoration materials, except Grade A, should be improved by one level on the basis of regulations.

8. Evacuate walkways and corridors

The ceilings of the horizontal evacuation walkways and exit halls of the above-ground buildings are decorated with Grade A materials, and other parts are decorated with materials not lower than Grade B 1; The ceiling, wall and floor of the evacuation walkway and exit hall of underground civil buildings should be decorated with Grade A materials.

9. Evacuate stairwells and vestibules

The ceiling, wall and floor of the evacuation stairwell and the front room should adopt Grade A decoration materials.

10. Exhibition venue

The decoration design of exhibition venues shall meet the following requirements:

1) The decoration grade of booth materials shall not be lower than B 1. ?

2) In the dining operation area where electric heating equipment is installed in the exhibition hall, the wall surface and operation table adjacent to the electric heating equipment shall be decorated with Grade A materials. ?

3) The materials adjacent to high-temperature lighting such as booths and tungsten halogen lamps shall be Grade A decorative materials.

1 1. Others

1) For the interior decoration of special high-rise buildings such as TV towers, the decorative fabric shall be made of no less than B 1, and all others shall be made of Grade A decorative materials.