Liquefied gas storage room is set independently.
Yes, the liquefied gas storage room should be set up independently. When the stored liquefied petroleum gas is less than 420kg (about 28 bottles 15kg liquefied petroleum gas), the gas cylinder room can be set in a single-story small room adjacent to the gas use place. For commercial users, restaurants and kitchens with liquefied gas exceeding 100kg, a separate room should be set up as a bottle storage room. The height of the room should be no less than 2.2 meters, and windows or vents should be provided. The lower edge of the room is not more than 0.2m from the indoor floor, and the area meets the pressure relief requirements, with good ventilation. Doors and windows should be opened outwards. There should be no doors, windows and holes communicating with the kitchen room, and doors directly leading to the outside should be set.