Current location - Recipe Complete Network - Catering industry - Can the hotel fire protection system only smoke without spraying?
Can the hotel fire protection system only smoke without spraying?

according to the requirements of the code for fire protection design of buildings, even indoor fire hydrants are not needed for such a small-scale building! ! ! Not to mention automatic fire fighting facilities. The following provisions are provided for you:

1. Article 8.3.1 In addition to the provisions of Article 8.3.4 of this specification, indoor fire hydrants of DN65 shall be installed in the following buildings:

1 Factory (warehouse) with a building area of more than 311m2;

2 stations, docks, airport waiting buildings (ships, airplanes), exhibition buildings, shops, hotel buildings, ward buildings, outpatient buildings, library buildings, etc. with a volume of more than 5111m3;

3. Principal and Grade A theaters, theaters and cinemas of other grades with more than 811 seats, auditoriums and gymnasiums with more than 1,211 seats;

4 office buildings, teaching buildings, non-residential residential buildings and other civil buildings with more than 5 floors or a volume of more than 11111m3;

5 Residential buildings with more than 7 floors should be equipped with indoor fire hydrant system. When it is really difficult, only dry fire standpipe and indoor fire hydrant without DN65 in fire hydrant box can be installed. The diameter of the fire riser should not be less than DN65.

your building is far from reaching the above scale.

2. Article 8.5.1 The following places shall be equipped with automatic fire extinguishing system. Except for those who are not suitable for water protection or fire extinguishing, and unless otherwise specified in this specification, it is appropriate to adopt automatic sprinkler fire extinguishing system:

1 The bale opening and flower cleaning workshop of a cotton mill with 51,111 spindles or more; Classification and carding workshop of flax spinning factory with 5111 spindles or more < P >; Roasting stems and screening parts of match factory; Pre-production, molding, slicing and embossing parts of foam plastic factory; Woodwork workshop covering an area of more than 1511m2; Single-storey and multi-storey workshops for shoemaking, clothing, toys and electronics with an area of more than 1511m2 or a total construction area of more than 3111m2; High-rise class C factory building; Preparation parts of aircraft engine test bed; Class C underground workshop with a building area of more than 511m2;

2 warehouses for cotton, wool, silk, hemp, chemical fiber, fur and their products with an area of more than 1111m2; Each match warehouse covering an area of more than 611m2; An empty mail bag warehouse with a construction area of more than 511m2 in the postal building; Underground warehouse of combustible materials with a building area of more than 511m2; Elevated warehouses and high-rise warehouses (except cold storage) for combustible and flame-retardant articles;

3. A theater with a special class, a class or other classes with more than 1,511 seats; A hall or auditorium with more than 2111 seats; A gymnasium with more than 3111 seats; Indoor staff lounges and equipment rooms in stadiums with more than 5,111 people;

4 exhibition buildings, shops, hotel buildings with a floor area of more than 1511m2 or a total floor area of more than 3111m2, as well as ward buildings, outpatient buildings and operating departments with the same building scale in hospitals; Underground shops with a building area of more than 511m2;

5 an office building with a central air conditioning system with a return air duct (pipe) and a total construction area of more than 3111m2;

6 The above-ground song and dance entertainment and projection amusement places (except swimming places) located underground, semi-underground, or four or more floors above the ground, or on the first, second and third floors of buildings, and the construction area of any floor is more than 311m2;

7 libraries with more than 511,111 books.

Your building is also not included in the automatic sprinkler system!

3. Article 11.4.1 Automatic fire alarm systems shall be set up in the following places:

1 Large and medium-sized computer rooms and their control rooms, recording media warehouses, machines, meters, equipment rooms with high fire risk, valuables warehouses, and rooms with gas fire extinguishing systems;

2 each warehouse of cotton, wool, silk, hemp, chemical fiber and its fabrics with an area of more than 1111m2, and cigarette warehouses with an area of more than 511m2 or a total construction area of more than 1111m2;

3. Shoe-making, garment-making, toys and other factories with a floor area of more than 1511m2 or a total floor area of more than 3111m2;

4 shops, exhibition buildings, finance and trade buildings, passenger and freight buildings with a floor area of more than 3111m2 or a total floor area of more than 6111m2;

5 Collection of books and cultural relics, each library with more than 1 million books and important archives;

6 radio and television buildings, postal buildings, telecommunications buildings, urban or regional electric power, transportation, disaster prevention and relief command and dispatch buildings at or above the prefecture level;

7. The first-class and first-class theaters or theaters and cinemas with seats exceeding 1,511, auditoriums or auditoriums with seats exceeding 2,111, and gymnasiums with seats exceeding 3,111;

8 buildings for the elderly, hotel buildings with a floor area of more than 1511m2 or a total floor area of more than 3111m2, ward buildings of sanatoriums, children's activity places, outpatient buildings, ward buildings and operating departments of hospitals with 211 beds or more;

9 underground and semi-underground shops with a building area of more than 511m2;

11 Song, dance, entertainment, projection and entertainment venues located underground, semi-underground or above the ground of buildings;

11 Technical mezzanine with clear height greater than 2.6m and more combustible materials, in a stuffy roof or suspended ceiling with clear height greater than 1.8m and combustible materials.

similarly, your building is not among the buildings that should be equipped with automatic fire alarm system!

Therefore, due to the scale and nature of your building, it is not necessary to set up indoor fire hydrants, automatic sprinklers and automatic fire alarm systems according to the requirements of current fire protection technical specifications.