Current location - Recipe Complete Network - Catering training - Six-story hotel, stand-alone building, with a total floor area of 1600 square feet, fire whether the automatic fire alarm system and fire sprinkler system to be installed
Six-story hotel, stand-alone building, with a total floor area of 1600 square feet, fire whether the automatic fire alarm system and fire sprinkler system to be installed
Not required.

First of all, the building height of 6 floors, the estimated height of not more than 24 meters, is not a high-rise building, should be applicable to the "building design fire code" (GB50016-2006 ). According to the specification of Article 8.5.1 "The following places should be set up automatic fire extinguishing system, in addition to water is not suitable to protect or extinguish the fire as well as other provisions of this code, it is appropriate to use automatic sprinkler system: ----------4 any floor floor area of more than 1500m2 or a total floor area of more than 3,000m2 of the exhibition building, store, hotel building, As well as hospitals in the same building size of the ward building, outpatient building, operating department; building area greater than 500m2 of the ground floor store;" the provisions of the hotel does not have the above, so it does not belong to the scope of the fire sprinkler system should be set up, if you set up the original, of course, better. Not set up, should meet the requirements of the code. If the design institute designed and approved by the audit that should be set up, such as the design may not be set up, such as the design and after the fire for the record qualified, still not installed, must be implemented for the online record of change procedures.

The specification of Article 11.4.1 provides that "the following places should be set up automatic fire alarm system: ---- 8 buildings for the elderly, any floor floor area of more than 1500m2 or a total floor area of more than 3,000m2 of the hotel building, nursing home wards, children's activities and greater than or equal to the 200-bed hospital outpatient clinic building, ward building, operating department, etc.;" "

The specification of the 11.4.1 article. building, operating department, etc.;", ibid, automatic alarm system installation is not required.

Of course, you mentioned the hotel if only catering is not a hotel, it is even less this must. Is a hotel, hotel, the evacuation stairs are indoor, must be closed stairwells, that is, stairwells installed Class B fire door.