Report on the incident of the fire shutter door falling off in the new factory I. Description of the accident
20 10 year 1 1 month 18 at about 2 pm 1# The fire shutter door on the south side of the east fire partition suddenly slipped.
Falling, the door panel and the reel fall off, causing the whole door panel to fall off, the side track is damaged, and the junction of the door and the fire door
Gypsum board falls off within 4 meters, the base fixed between the door rolling machine and the bottom plate breaks into three pieces, and the motor falls off. Incident
At that time, there were no personnel in and out of the door, and no personnel safety accidents occurred.
Second, the accident treatment
After the incident, the project department rushed to the scene for accident analysis and evidence collection, and at the same time contacted the manufacturer in time to organize relevant personnel.
Go to the scene for accident treatment. On the same day, the manufacturer organized the installation personnel to deal with the problem door in time, which ensured the health
Orderly production. At the same time, the manufacturer is ordered to organize relevant technical personnel to study and analyze the door-falling incident and submit it.
Accident analysis report. At the same time, the quality problems (equipment quality, installation quality) reflected by this door-falling incident are corrected.
All other fire shutter doors in a new factory should be thoroughly investigated and repaired.
With 20 10 1 1 22 at 4: 00 p.m. in the conference room on the third floor of the new factory, an accident symposium was held with the manufacturer.
Discussion, factory attendance 1 person. Because the manufacturer was not a professional, there was no recognition of the cause of the incident.
Set. At the end of the meeting, the manufacturer was asked to provide the following eight items and hand them in before Thursday. Cause analysis of (1) sudden sliding down of rolling shutter door.
(2) Analysis of the reasons why the shutter door plate and the reel fall off.
(3) Standards for manufacturers to install fire shutter doors,
(4) The original construction drawings.
(5) Acceptance data of the opposite door after the construction.
(6) Prepare to sign a warranty commitment letter,
(7) Draw up a plan for the inspection and renovation of all other fire doors. customer service
(8) Submit a complete set of instructions on the use and maintenance of fire shutter doors. Third, the accident analysis: